TECHNICAL DATA
RATINGS
- Rated current ( In ) : 5 A
- Rated frequency : 50 Hz Burden : < 0.3 VA at In
- Thermal withstand : 4 x In continuous
AUXILIARY SUPPLY
- Model K204A-240A : 198 ~ 265 V AC
- Model MK204A-110A : 94 ~ 127V AC
- Supply frequency : 50 Hz VA rating : 3 VA typical
SETTING RANGES
- Low-set ( I > ) : 2.0 A to 6.0 A : 40% to 120%
- Time multiplier ( TM ) : 0.05 to 1.0
- High-set ( I >> ) : I > to 10 x I > or disable
- High-set delay time (t >>) : Instantaneous
CONTACTS
- Trip contact (R1) : Manual reset type
- Contact Arrangement : Change-over
- Contact rating : 5 A, 250 V AC ( cosϕ = 1 )
- Contact material : Silver alloy
- Expected electrical life: 100,000 operations at rated current
- Expected mechanical life: 5 x 106 operations
INDICATORS
- Auxiliary supply : Green indicator
- Pick-up : Red indicator
- Trip : Red indicator
PERFORMANCE
- Adjustable accuracy : Less than ±5%.
- Repeatability : Less than 0.5% of full scale.
- MECHANICAL Mounting : Panel mounting
- Front panel : Standard DIN 96 mm x 96 mm
- Approximate weight : 0.7 kg
ENVIRONMENTAL CONDITIONS
- Temperature : -5˚C to +55˚C
- Humidity : 56 days at 93%
- RH and 40˚C non-condensing