TECHNICAL DATA
DISPLAY TYPE
- LCD display
MEASUREMENTS
- 3-phase 4-wire system
- 3-phase 3-wire system
CURRENT MEASUREMENT
- CT primary : 5 ~ 8000 A
- CT secondary : 5 A
- Minimum measurement : 5 mA
- Accuracy : 0.5% from 1A to 6 A (secondary)
- Burden : < 0.05 VA at 5 A
- Sustained overload : 6 A
VOLTAGE MEASUREMENT
- Nominal phase voltage : 20 ~ 300 V AC
- Minimum measurement : 10 V
- Accuracy : 0.5% at full scale
- Phase voltage via VT : 60 ~ 33,000 V
POWER MEASUREMENT
- Real power, apparent power, reactive power measurement
- Measuring updating period : 1 s
- Accuracy : 1.0%
ACTIVE POWER DEMAND
- Interval : 1 ~ 30 mins
POWER FACTOR MEASUREMENT
- Total and displacement power factor
- Accuracy : 1.0%
FREQUENCY MEASUREMENT
- Measurement range : 45 ~ 65 Hz
- Measurement updating period : 1s
- Accuracy : 0.5%
ENERGY ACCURACY
- Active (according to IEC 62053-21) : class 1
- Reactive (according to IEC 62053-23) : class 2
AUXILIARY POWER SUPPLY
- AC voltage : 90 ~ 415 V AC
- Frequency : 50 / 60 Hz
- DC voltage : 100 ~ 300 V DC
- Power consumption : <3 VA
COMMUNICATION
- Hardware interface : Isolated RS485
- Protocol : Modbus-RTU
- Baud rate : 2400, 4800, 9600,19200, 38400
ENVIRONMENTAL CONDITIONS
- Operating temperature : -10˚C ~ +55˚C
- Storage temperature : -20˚C ~ +70˚C
- Humidity : 0 – 95%,non condensing
MECHANICAL
- Mounting : Panel mounting
- Dimension (mm) : 96(w) x 96(h) x 100(d)
- Approximate weight : 0.5 kg