TECHNICAL DATA
WIRING SYSTEMS
- 3-phase 4-wire system
- 3-phase 3-wire system
- Nominal current : 5 A
- Min. measurement : 5 mA
- Accuracy : 0.2% of full scale
- Burden : < 0.05 VA at 5 A
- Measurement range : 10 A
- Pulsed withstand : 100 A for 1 sec
- CT primary : 5 ~ 50,000 A
- Nominal phase voltage : 0 ~ 300 V AC
- Minimum measurement : 10 V
- Accuracy : 0.2% at full scale
- Phase voltage via VT : 60 ~ 50,000 V
POWER MEASUREMENT
- Real power, apparent power, reactive power
- Accuracy : 0.5%
POWER FACTOR MEASUREMENT
- Total and displacement power factor
- Accuracy : 0.5%
POWER & THERMAL CURRENT DEMAND
- Interval : 1 ~ 30 mins
VOLTAGE AND CURRENT SEQUENCE
- Positive, negative and zero sequence
FREQUENCY MEASUREMENT
- Measurement range : 45 ~ 65 Hz
- Accuracy : 0.2%
- ENERGY MEASUREMENT ACCURACY
- Active : IEC 62053-22 class 0.5
- Reactive : IEC 62053-23 class 2
HARMONICS DISPLAY
- Fundamental up to 32nd order
DISPLAY
- Simultaneous 3-phase voltage or current waveforms
COMMUNICATION
- Protocol : Modbus RTU
- Interface : Isolated RS485
- Protocol : Modbus TCP/IP
- Interface : Ethernet 10M/100M BaseT
- Protocol : HTTP Server
- Interface : Ethernet 10M/100M BaseT
AUXILIARY POWER SUPPLY
- AC voltage : 90 ~ 415 V AC
- Frequency : 50 / 60 Hz
- DC voltage : 100 ~ 300 V DC
- Power consumption : 3W typical
- Sustained overload : 500 V AC
ENVIRONMENTAL CONDITIONS
- Overvoltage category : IV
- Pollution degree : 2
- Operating temperature : -10˚C ~ +55˚C
- Storage temperature : -20˚C ~ +70˚C
- Humidity : 0 – 95%,non condensing
MECHANICAL
- Mounting : according to DIN 43700 /
- ANSI C39.1
- Dimension (mm) : 96(w) x 96(h) x 100(d)
- Enclosure protection : IP63 at the panel
- IP20 at the body
- Approximate weight : 0.5 kg